CVE-2026-11826
概要

OpenPLC_v3 contains a heap-based buffer overflow in the getData() function in webserver/core/modbus_master.cpp. getData() reads characters between two delimiters into a caller-supplied buffer with no size parameter and no bounds check. In parseConfig() the function is invoked with the 100-byte heap-allocated MB_device.dev_name field. An authenticated attacker with access to the OpenPLC web interface can send a crafted HTTP POST to the /modbus endpoint with an oversized device_name value; the value is persisted to mbconfig.cfg and parsed on load, overflowing dev_name and overwriting adjacent struct fields (protocol at offset 108, dev_address at offset 109, ip_port at offset 210). A 200-byte payload writes 100 bytes past the allocation. The result is heap corruption leading to runtime crash and denial of service of the PLC process control loop, with attacker-controlled overwrite of adjacent configuration fields. The upstream repository was archived on 2026-04-04 and no fix is expected; the vendor has confirmed the issue does not affect OpenPLC Runtime v4.

公表日 2026年7月18日23:17
登録日 2026年7月19日4:18
最終更新日 2026年7月21日2:17
CVSS3.1 : HIGH
スコア 8.8
ベクター CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
攻撃元区分(AV) ネットワーク
攻撃条件の複雑さ(AC)
攻撃に必要な特権レベル(PR)
利用者の関与(UI) 不要
影響の想定範囲(S) 変更なし
機密性への影響(C)
完全性への影響(I)
可用性への影響(A)
関連情報、対策とツール
共通脆弱性一覧